CHILLERS
FRIGOSMART
MAXI
FRIGOSMART MAXI
MAXI | MAXI | MAXI | MAXI | MAXI | MAXI | |||
1050 | 1060 | 1070 | 1080 | 1100 | 1125 | |||
CRITERIA 1 | COOLING CAPACITY | kW | 108,4 | 136 | 158,3 | 180,1 | 243 | 298 |
Twater,in. = 12°C | kCal/h | 93.224 | 116.960 | 136.138 | 154.886 | 208.980 | 256.280 | |
Twater,out. = 7°C | POWER INPUT | kW | 37,52 | 48,02 | 54,52 | 64,38 | 81,88 | 101,54 |
Tambient = 35°C | C.O.P. | 2,89 | 2,83 | 2,9 | 2,8 | 2,97 | 2,93 | |
CRITERIA 2 | COOLING | kW | 130,8 | 164,1 | 193,4 | 221 | 293 | 358 |
Twater,in. = 15°C | kCal/h | 112.488 | 141.126 | 166.324 | 190.060 | 251.980 | 307.880 | |
Twater,out. = 10°C | POWER INPUT | kW | 35,32 | 45,22 | 51,32 | 61,98 | 77,38 | 95,14 |
Tambient = 28°C | C.O.P. | 3,7 | 3,63 | 3,77 | 3,57 | 3,79 | 3,76 | |
CRITERIA 3 | COOLING CAPACITY | kW | 157,2 | 197,3 | 234 | 267 | 352 | 429 |
Twater,in. = 20°C | kCal/h | 135.192 | 169.678 | 201.240 | 229.620 | 302.720 | 368.940 | |
Twater,out. = 15°C | POWER INPUT | kW | 36,92 | 47,12 | 53,32 | 65,68 | 80,58 | 99,24 |
Tambient = 25°C | C.O.P. | 4,26 | 4,19 | 4,39 | 4,07 | 4,37 | 4,32 | |
GENERAL INFORMATIONS | ||||||||
NUMBER OF COMPRESSOR | n | 1 | 1 | 1 | 1 | 1 | 1 | |
NUMBER OF FAN x DIMENSION | n x mm | 8 x 500 | 4 x 800 | 4 x 800 | 6 x 800 | 6 x 800 | 8 x 800 | |
WATER FLOW RATE | m³/h | 22,5 | 28,23 | 33,26 | 38,01 | 50,4 | 61,58 | |
l/min | 375 | 470,4 | 554,4 | 633,5 | 839,9 | 1.026,30 | ||
LENGTH | mm | 3.200 | 3.100 | 3.300 | 3.500 | 4.100 | 4.800 | |
WIDTH | mm | 1.850 | 2.300 | 2.300 | 2.300 | 2.300 | 2.300 | |
HEIGHT | mm | 2.050 | 2.260 | 2.260 | 2.260 | 2.260 | 2.260 | |
PIPING CONNECTIONS | DN | 80 | 80 | 80 | 100 | 125 | 125 |